Airconditioning

 
Quartz Active Chilled Beam Cassette, Cassette Fan Coil Units, Wall Mounted Fan Coil Units, Floor/Ceiling Mounted Fan Coil Units(FCUs)-Chassis and Cased

 All Quartz products shown are supported on our Principals' websites with full technical manuals. www.quartz.co.uk

 



Existing Active Chilled Beam Systems

existing systems diagram

Warm room air rising through a ceiling grille by natural convection and then through a chilled beam coil where it is cooled and induced back into the room by the negative pressure caused by the velocity of the air being introduced into the room via the fresh air duct nozzles.

One of the problems with this system is, that as the room temperature and humidity increases, condensation can form on the coil and then drip from the coil through the grille and into the room below.

The only way to avoid this is to increase the temperature of the water passing through the coil, which in turn reduces the cooling capacity of the chilled beam. (Just when the customer needs it most!)

Another disadvantage is to get adequate cooling the coil has to be 2 to 3m long which is sometimes difficult for an Architect to fit with his ceiling layout. Quartz have, by turning the coil through 90°, (i.e. turning it on its side) and then bending it into a square shape greatly reduced the space needed in the ceiling grid for the same cooling output.

Also, by turning the coil on its side, a drip tray channel facilitates the  collection and removal of any condensate produced by the coil sweating, thus removing the necessity of reducing the cooling capacity of the cooling coil as temperature and humidity increase. It is this condensate removal that we feel may be possible to patent.

Quartz Active Chilled Beam Cassette System (CBC)

The Chilled Beam Cassette, originally introduced at the CIBSE/ASHRAE Conference in Edinburgh in 2003 under the Marstair Airking brand, was changed to the Quartz Chilled Beam Cassette when Marstair took over Quartz at the beginning of 2005. The fascia on the left is the standard cassette fascia common to both the Quartz chilled water cassettes and the Marstair DX cassettes. The fascia on the right is one of the architecturally aesthetic options. There is no reason why the client or architect cannot choose and indeed devise a fascia to integrate with the false ceiling manufacturer. Quartz would be pleased to assist with this. Further developments have now taken place for a four pipe heating and cooling version and, in conjunction with Thorn, a version with lighting is also available.

Mastair airconditioning


The principle of operation is simple. Primary air fed into a plenum chamber is discharged through an arrangement of strategically placed nozzles. This in turn induces secondary room air through the cooling coil within the unit. Efficiencies are high, as the primary air constitutes only 25% of the total air volume, the remaining 75% volume from the resultant induced air.



The Chilled Beam Cassette also has the added advantage of being able to operate at chilled water temperatures below due point (typically chilled water less than 14C). This results in increased performance. Condensate removal is possible via the standard gravity drain feature or the optional internal pump lift.

The Quartz Chilled Beam Cassette (patent pending) combines all the proven features of our range of Chilled Water Cassettes fan coils, and the benefits of Active Chilled Beams.

Designed for rapid installation into a standard ceiling grid, the Chilled Beam Cassette utilises a one-piece structural chassis with integral wipe clean drain tray. The chassis, once removed, allows easy access to all sides of the coil for cleaning.

The duty of the CBC ranges from 400 watts with a nominal of 825 watts to a maximum of 1200 watts, suitable for the inner core of the building. Where high duties are required, on the periphery of the building, the Quartz Chilled Water Cassette can be used to provide a much greater duty. The fascias of the Chilled Beam Cassette (CBC) and the Chilled Water Cassette (CWC) can be exactly the same.


KEY BENEFITS

  • Condensate can be removed
  • Low temperature water can be used
  • Low installation cost
  • Ultra quiet operation
  • High system COP
  • Easy filter access
  • 4 way discharge
  • Integral, easy to clean drain tray
  • Ideal for use with 'free cooling' chillers






Quartz have a full range of Chillers (inclusive of free cooling and heatpump.) Also a full range of Cassettes, Fan Coil Units and Plastic Bodied Wall Mount Fancoil Units (FCUs). 
 

Quartz CWC/ H 600 - Chilled Water Cassette (FCUs) 1 to 4kW

 

Ideal for smaller shops and offices, these cassettes are specifically designed to allow installation into a standard suspended ceiling grid.

 

Standard Features

  • Lightweight removable chassis 0 3 or 4 way discharge capability

  • Pipe connection for gravity condensate drain (optional pumps)

  • LPHW heating circuit (CWCH)

  • Low sound levels

  • Long life washable filters

  • Suitable for branch duct applications o Fan finger guard

  • Fresh air inlet


Quartz CWC/ H 875 - Chilled Water Cassette (FCUs) 3.8 to 8kW

 

Shopping centres and open plan offices are prime locations for these cassettes, which are designed to facilitate rapid installation.

 

SINGLE LARGE DIAMETER FAN

 

Standard Features

  • Lightweight removable chassis

  • 3 or 4 way discharge capability

  • Pipe connection for gravity condensate drain (optional pumps)

  • LPHW heating circuit (CWCH)

  • Long air throws

  • Low sound levels

  • Long life washable filters

  • Suitable for branch duct applications

  • Fan finger guard

  • Fresh air inlet


Quartz CWM - Chilled Water Wall Mounted Fan Coil Units1.5 to 4.8kW

 

Hi-level front airflow, to minimise draughts, and fresh styling distinguish these units, which are ideal for larger commercial and retail applications.

 

Standard Features

  • High wall mounted hi-level front airflow

  • Low sound levels

  • Adjustable air deflectors

  • Long life, flexible, washable filters


 

Quartz CBC - Active Chilled Beam Cassette (Metallic Fascia illustrated with a luminaire)

 

The Quartz Chilled Beam Cassette (Patent Pending) combines all the proven features of our range of Chilled Water Cassette fan coils, and the benefits of Active Chilled Beams.

 

ACTIVE CHILLED BEAM CASSETTE

 

Standard Features

  • Pipe connection for gravity condensate drain (optional pump)

  • Low temperature water can be used

  • Low installation cost

  • Ultra quiet operation

  • High system COP

  • Easy filter access

  • 4 way discharge

  • Integral, easy to clean drain tray

  • Ideal for use with 'free cooling' chillers

The full technical details of all the fancoil units can be found in our catalogue entry in kellysearch.www.kellysearch.com



Quartz Sapphire - Waterside Control Fan Coil Units (FCUs)

 

A versatile, high power fan coil unit that meets demanding heating and cooling requirements, providing discreet, effective and reliable climate control.

 

270MM DEEP DUCTED FAN COILS

 

Standard Features

  • Filters

  • Class '0' fire-rated insulation

  • Flush panelled, extra rigid casing

  • Easy access protected control enclosure

  • High performance fans


Quartz Amber - Horizontal Waterside Control Fancoil Units (FCUs)

 

A very compact, high power fan coil unit that meets exacting' heating, cooling and noise requirements. Units incorporate the patented `free flow' condensate tray.

 

235MM DEEP DUCTED FAN COILS

 

Standard Features

  • Low maintenance filter

  • Class '0' fire-rated insulation

  • High output 'optimised' components

  • Flush panelled, extra rigid casing

  • Mitred space saving plenum

  • 27 speed auto transformer speed control

  • Easy access protected control enclosure

  • High performance fans

  • Stainless steel removable drain pan


Quartz Amethyst Waterside Control Fan Coil Units (FCUs)

 

A 175mm deep slim-line version of the very successful Amber range of ceiling mounted horizontal fan coil units.

 

175MM DEEP SLIM- LINE DUCTED FAN COILS

 

Standard Features

  • Low maintenance filter

  • Class '0' fire-rated insulation

  • High output 'optimised' components

  • Flush panelled, extra rigid casing

  • Mitred space saving plenum

  • 27 speed auto transformer speed control

  • Easy access protected control enclosure

  • High performance fans

  • Stainless steel removable drain pan


Quartz Diamond - Airside Control Fan Coil Units (FCUs)

 

An ultra compact, high power fan coil that meets some very exacting heating and cooling requirements, providing discreet, effective climate control.

 

235MM DEEP AIRSIDE CONTROL FAN COILS

 

Standard Features

  • Low maintenance filter

  • Stainless steel removable drain pan

  • High efficiency airside control (air path diverter)

  • Flush panelled, extra rigid casing

  • 27 speed auto transformer speed control

  • Class `0' fire-rated insulation

  • Easy access protected control enclosure

  • Mitred space saving plenum

  • High performance fans



Quartz CWF - Chilled Water Fan Coil Unit 0.5 to 9.8kW (Horizontal and Vertical, Chassis or Cased with a Polyester powder coating)

Fan Coil Casings
We, as agents for both Quartz and BGP Services Ltd., can coordinate the design/instsallation of continuous fan coil enclosure casings and fancoil units. This is particularly useful for design engineers confronted with hotel refurbishments and 1960/1970 office block designs with low FFL to ceiling heights. (Please see the Trench Perimeter/Fancoil Casing section of this website.)

Ideal for hotels, larger offices, retail sales areas and major refurbishment projects. These units can

be floor, wall or ceiling void mounted, or ceiling suspended.

 

HORIZONTAL AND VERTICAL

 

Standard Features

  • Low sound levels

  • Vertical and horizontal models

  • Chassis and cased (painted sheet steel) versions

  • Easily removable/washable filters

  • Multi-speed motor

  • Easy installation and maintenance


 

Quartz Chillers - Air Cooled Chillers and Heat Pumps 5 to 800kW

 

AIR COOLED PACKAGED

 

Range Features

  • Units are fitted with scroll or screw compressors

  • Polyester powder coated finish

  • Mains isolator

  • Condenser coil with copper tubes and corrugated aluminium fins with metal

protection guard

  • Direct drive axial fans (IP54) with overload protection

  • Stainless steel plate heat exchanger (AISI316) or shell in tube exchanger

  • Microprocessor control

  • Flow switch

  • Heat pump version (H) supplied with 4 way reversing valve, liquid receiver

second thermostatic expansion valve, automatic defrosting system

  • Integrated hydraulic kit version (K) supplied with buffer tank, water pumps)

  • Low noise version

  • Free cooling version


Quartz Aqua Systems


Aqua 4 Image

Four Pipe Fan Coil System

Intelligent 4-pipe FCU system served by 2 (or more) air to water reverse cycle heat pump chillers, suitable for multi-zone simultaneous heating / cooling applications.

  • 70 / 30 FCU split coil flexibility
  • Communicating trend control system
  • No pipe run / lift limitation
  • No limit to number of indoor units
  • Heat recovery can be integrated into the system
  • AQUA 4 sizing software will ensure correct selection and orientation of indoor units.



diagram 1

All heating

Only requirements for heating exist in the building and both outdoor units provide hot water to all coil sections, as required.



Diagram 2

Simultaneous heat and cool

The primary heating heat pump is providing hot water and the primary cooling heat pump is supplying cold water and the respective coil sctions are activated. Zone requirements, heat pump mode, valve actuation and fan speed are all controlled automatically by the integral control system.



diagram 3

All Cooling

Only requirements for cooling exist, both outdoor units provide cold water to all coil sections, as required.



Aqua 2 Plus Image
Four Pipe Fan Coil System

4-pipe FCU system served by conventional air cooled chillers and seperate boiler systems Suitable for multi-zone simultaneous heating / cooling applications.

  • 70 / 30 FCU split coil flexibility
  • Communicating trend control system
  • No pipe run / lift limitation
  • No limit to number of indoor units
  • Systems 12-500kW, 16 chiller models


    Diagram 4

    *The larger section of the indoor coil is connected to the chilled water and the smaller to the LPHW.

    Simultaneous Heat and Cool

    A cooling requirement exists in Zone 2.
    The boiler is providing hot water and the chiller is supplying cold water.
    The respective coil sections are activated to cool Zone 1 and to heat Zone 2.
    Determination of Zone requirement, valve actuation and fan speed are all monitored and controlled automatically by the integral control system.

    Aqua 2 Image

    Two Pipe Fan Coil Systems

    Innovative 2-pipe system with FCU's served by air to water reverse cycle heat pumps suitable for large zone with no heating / cooling conflict.

    • 70 / 30 FCU split coil for variable capacity
    • Communicating Trend control system
    • reverse cycle heat pump / system capacities 12-500kW & multiples thereof


    Diagram 5

    Zone control - Heating Mode (All outdoor units on heating)

    Stage 1 Zone temperature is >0.2°C below set point. Valve 1 would be open, utilising the 30% coil segment

    Stage 2
    Zone temperature is >0.6°C below set point. Valve 1 would be closed and Valve 2 open, utilising the 70% coil segment

    Stage 3
    Zone temperature is >1.0°C below set point. Both Valves 1 and 2 would be open, utilising the full coil segment

    Stage 4
    Zone temperature is >1.4°C below set point. Valve 1 would be open and fan speed would be switched to high.

    Zone control - Cooling Mode (All outdoor units cooling)

    In cooling mode, the system operation is identical to that for heating but activated for zone temperatures above set point. All outdoor units will be operating on coolings.



    Aqua Multi Image

    Two Pipe Fan Coil System

    2-pipe system with FCU for cooling only.

    • Individual FCU or group zone control
    • Single point responsibility
    • Communicating Trend controls
    • No limitation on pipe runs / lift
    • No limitation to the number of indoor units


    Diagram 6

    Zone Control - Cooling Only

    Stage 1 Zone temperature is >0.2°C below set point. Valve 1 would be open, utilising the 30% coil segment

    Stage 2
    Zone temperature is >0.6°C below set point. Valve 1 would be closed and Valve 2 open, utilising the 70% coil segment

    Stage 3
    Zone temperature is >1.0°C below set point. Both Valves 1 and 2 would be open, utilising the full coil segment

    Boost Cooling Should the zone temperature exceed 1.4°C above the set point, both valves will be open and fan will automatically switch to high speed.
  •  

    Hitachi

    Hi-Velocity System

    ACS Wall Mounted

    ACS Cassette